RIF-1-RPT-LDP-24DC/1IC Relay Module

2909884

Preassembled relay module with Push-in connection, consisting of: relay base, power contact relay, plug-in display/interference suppression module, retaining bracket. Contact switching type: 1 N/O contact, max. inrush current up to 130 A peak, 80 A (20 ms), 24 V DC input voltage

Notes on operation FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in bridge for the output side (11/21)

Product type Relay Module
Product family RIFLINE complete
Application high inrush currents
Operating mode 100% operating factor
Mechanical service life 3x 107 cycles
Insulation characteristics
Insulation Safe isolation, reinforced insulation
Insulation characteristics: Standards/regulations
Insulation Safe isolation, reinforced insulation
Overvoltage category III
Pollution degree 2

Maximum power dissipation for nominal condition 0.43 W
Test voltage (Winding/contact) 4 kV AC (50 Hz, 1 min., winding/contact)
Standards/regulations
Rated insulation voltage 250 V AC
Rated surge voltage 6 kV

Coil side
Nominal input voltage UN 24 V DC
Input voltage range 19.2 V DC ... 33.6 V DC (20 °C)
Input voltage range in reference to UN see diagram
Drive and function monostable
Drive (polarity) polarized
Typical input current at UN 18 mA
Typical response time 8 ms
Typical release time 10 ms
Coil voltage 24 V DC
Protective circuit Freewheeling diode; Freewheeling diode
Operating voltage display Yellow LED

Switching
Contact switching type 1 N/O contact
Type of switch contact Single contact
Contact material AgSnO
Maximum switching voltage 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage 12 V (100 mA)
Limiting continuous current 6 A
10 A (Value is permissible if connections 11 and 21, as well as connections 14 and 24 are bridged.)
Maximum inrush current 80 A (20 ms)
130 A (peak, at capacitive load, 230 V AC, 24 μF)
Min. switching current 100 mA (12 V DC)
Interrupting rating (ohmic load) max. 264 W (at 24 V DC, observe contact derating)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
2750 VA (at 250 V AC, observe contact derating)
Switching capacity min. 1200 mW
Utilization category CB Scheme (IEC 60947-5-1) AC15, 6 A/250 V (N/O contact)
DC13, 2 A/24 V (N/O contact)

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section rigid 0.14 mm² ... 1.5 mm²
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG 26 ... 16 (solid)
26 ... 16 (flexible)

Drill hole
Diameter 3.2 mm
Width 16 mm
Height 96 mm
Depth 75 mm

Color gray (RAL 7042)

Ambient conditions
Degree of protection (Relay base) IP20 (Relay base)
Degree of protection (Relay) RT III (Relay)
Degree of protection (Installation location) ≥ IP54 (Installation location)
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m

Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

Standards/regulations
Standards/regulations IEC 60947-5-1

RIF-1-RPT-LDP-24DC 1IC - Relay Module