PT 2-TELE - Surge protection device

2024-05-07T06:39:26Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:12136702686591924689133@q83q.8c1312om

 

PT 2-TELE Surge protection device

2882828

Surge protective device, consisting of plug and base element, for protecting a double wire from analog and digital telecommunications interfaces (VDSL up to 50 Mbps, on short paths (< 300 m) up to 100 Mbps).

Surge protection plug for DIN rail mounting, 2-section pluggable, normal mode voltage coarse and fine protection for 2-conductor analog telecommunication interface as well as common mode voltage coarse protection to ground.

Product type Surge protection for information technology
Product family PLUGTRAB PT
IEC test classification B2
C1
C2
C3
D1
Type DIN rail module, two-section, divisible
Number of positions 2
Surge protection fault message none
Wire pairs per module 1
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal voltage UN 185 V DC
130 V AC

Connection method Screw connection
Screw thread M3
Tightening torque 0.5 Nm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section rigid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12

Dimensional drawing
Width 17.7 mm
Height 90 mm
Depth 65.5 mm
Horizontal pitch 1 Div.

Color black (RAL 9005)
black (RAL 9005)
Flammability rating according to UL 94 V-0
Housing material PA 6.6

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Earth Ground
Maximum continuous voltage UC 185 V DC
130 V AC
Rated current 450 mA AC (45 °C)
130 mA DC (45 °C)
Operating effective current IC at UC ≤ 10 µA
Residual current IPE ≤ 10 µA
Nominal discharge current In (8/20) µs (line-line) 10 kA
Nominal discharge current In (8/20) µs (line-ground) 10 kA
Pulse discharge current Iimp (10/350) µs (line-line) 1 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 1 kA
Total discharge current Itotal (8/20) µs 18 kA
Max. discharge current Imax (8/20) µs maximum (line-earth) 18 kA
Nominal pulse current Ian (10/700) µs (line-line) 100 A
Nominal pulse current Ian (10/700) µs (line-earth) 100 A
Output voltage limitation at 1 kV/µs (line-line) spike ≤ 300 V
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 300 V
Output voltage limitation at 1 kV/µs (line-line) static ≤ 300 V
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 300 V
Residual voltage at In (conductor-conductor) ≤ 160 V (C2 - 10 kV / 5 kA)
Residual voltage at In (conductor-ground) ≤ 200 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (line-line) ≤ 250 V (B2 - 1 kV / 25 A)
≤ 300 V (B2 - 4 kV / 100 A)
≤ 270 V (C1 - 1 kV / 500 A)
≤ 300 V (C2 - 2 kV/1 kA)
≤ 320 V (C2 - 4 kV / 2 kA)
≤ 330 V (C2 - 10 kV / 5 kA)

PT 2-TELE - Surge protection device