AXL F RTD8 1F Temperature module

2688077

Axioline F, Temperature recording module, Analog inputs: 8 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors

The module is designed for use within an Axioline F station. It is used to acquire signals from resistive temperature sensors. The module supports all common platinum and nickel sensors in accordance with DIN EN 60751 and SAMA. Cu10, Cu50, Cu53 sensors as well as various KTY8x sensor types are also supported.

Dimensional drawing
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps

Module
Input address area 16 Byte
Output address area 16 Byte
Required parameter data 20 Byte
Required configuration data 6 Byte

Analog
Input name Analog inputs
Description of the input Inputs for resistive temperature sensors
Number of inputs 8 (for resistance temperature detectors)
Connection method Push-in connection
Connection technology 2-, 3-, 4-conductor (shielded)
A/D converter resolution 24 bit
Sensor types (RTD) that can be used Pt, Ni, KTY, Cu sensors
Data formats IB IL, S7-compatible
Measured value representation 16 bits (15 bits + sign bit)
Input filter time 40 ms
60 ms
100 ms
120 ms (adjustable)
Nominal value of the current sources 1 mA (Pt 100, Ni 100, RLin 500 Ω; pulse current, the specification is valid during the sampling phase)
210 µA (P t1000, Ni 1000, RLin 5000 Ω; pulse current, the specification is valid during the sampling phase)
Differential non-linearity typ. 1 ppm / ±0.0001 % (in all ranges)
Integral non-linearity typ. 30 ppm / ±0.003 % (Pt 100)
typ. 20 ppm / ±0.002 % (RLin 500 Ω)
typ. 200 ppm / ±0.02 % (RLin 5000 Ω)
Linear resistance measuring range 0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
Protective circuit Short-circuit protection, overload protection of the inputs
Transient protection of inputs
Transient protection of sensor supplies

Product type I/O component
Product family Axioline F
Type block modular
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Maximum power dissipation for nominal condition 0.9 W
Potentials
Power consumption typ. 0.94 W (at UBus and UA (up to HW 06))
typ. 0.59 W (at UBus and UA (from HW 07))
max. 1.5 W (at UBus and UA (up to HW 06))
max. 1.03 W (at UBus and UA (from HW 07))
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 180 mA (up to HW 06)
max. 85 mA (from HW 07)
typ. 115 mA (up to HW 06)
typ. 60 mA (from HW 07)
Power consumption max. 900 mW (up to HW 06)
max. 425 mW (from HW 07)
typ. 580 mW (up to HW 06)
typ. 300 mW (from HW 07)
Potentials: Supply for analog modules (UA)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 25 mA
typ. 15 mA (up to HW 06)
typ. 12 mA (from HW 07)
Power consumption max. 0.6 W
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode