PLC-HSC-24DC/230AC/10 Solid-state relay

2905214

PLC-INTERFACE, hybrid solid-state relay incl. bypass relay with screw connection, for mounting on NS 35/7,5 DIN rail, input: 24 V DC, output: 24 V AC - 253 V AC/10 A

Product type Solid-state relay module
Product family PLC-INTERFACE
Application Output function
Operating mode 100% operating factor
Insulation characteristics
Insulation safe isolation
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation safe isolation
Overvoltage category III
Pollution degree 2

Test voltage 4 kVrms (50 Hz, 1 min., winding/contact)
Air clearances and creepage distances between the power circuits
Rated insulation voltage 260 V AC
Rated surge voltage 6 kV

Rated control circuit supply voltage US 24 V DC
Voltage range with reference to US 0.8 ... 1.2
Rated control supply current IS ≤ 19 mA
Rated actuating voltage UC 24 V DC
Voltage range with reference to UC 0.8 ... 1.2
Rated actuating current IC 6.8 mA
"0" signal switching threshold in reference to UC < 0.4
"1" signal switching threshold in reference to UC > 0.8
Typical response time 30 ms
Typical turn-off time 20 ms
Status display Yellow LED
Protective circuit Reverse polarity protection
Surge protection
Surge voltage protection > 33 V DC
Transmission frequency 1 Hz

Designation AC hybrid output
Contact switching type 1 N/O contact
Design of digital output electronic
Output voltage range 24 V AC ... 253 V AC (50/60 Hz)
Limiting continuous current 10 A (see derating curve)
Min. load current 100 mA
Leakage current < 1 mA
Surge current 250 A (tp = 20 ms, at 25 °C)
Max. load value 350 A2s (tp = 10 ms, at 25 °C)
Surge voltage protection > 275 V
Output circuit 2-conductor, floating
Protective circuit Varistor

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)
Conductor cross section AWG 26 ... 14
Tightening torque 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing))

Width 14 mm
Height 80 mm
Depth 94 mm

Color gray (RAL 7042)

Ambient conditions
Degree of protection (Relay base) IP20 (Relay base)
Degree of protection (Relay) RT II (Relay)
Degree of protection (Installation location) IP54 (Installation location)
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m

Corrosive gas test
Identification ISA-S71.04. G3 Harsh Group
EN 60068-2-60

PLC-HSC-24DC 230AC 10 - Solid-state relay