Email verifiedBusiness License verified

IL EIP BK DI8 DO4 2TX-PAC - Bus coupler

2024-05-08T07:20:36Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:4642721267135102911691@2q111q.7c85om

 

IL EIP BK DI8 DO4 2TX-PAC Bus coupler

2897758

Inline, Bus coupler, EtherNet/IP™, RJ45 jack, Digital inputs: 8, 24 V DC, connection technology: 3-conductor, Digital outputs: 4, 24 V DC, 500 mA, connection technology: 3-conductor, transmission speed in the local bus: 500 kbps / 2 Mbps, degree of protection: IP20, including Inline connectors and marking fields

The bus coupler with integrated I/Os is intended for use within an EtherNet/IP™ network and represents the link to the Inline I/O system. Up to 61 Inline devices can be connected to the bus coupler. The bus coupler supports a maximum of 8 PCP devices. A corresponding EDS file is available for integrating the Inline station into the programming system. This file can be downloaded via the product at www.phoenixcontact.com/products.

Dimensional drawing
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Specfications with connectors

Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.

EtherNet/IP™
Number of interfaces 2
Connection method RJ45 jack
Note on the connection method Auto negotiation and autocrossing
Permissible conductor cross section 0.14 mm² ... 0.22 mm² (twisted pair)
Transmission speed 10/100 Mbps (half or full duplex (automatic detection))
Transmission physics Ethernet in RJ45 twisted pair
Inline local bus
Number of interfaces 1
Connection method Inline data jumper
Transmission speed 500 kbps / 2 Mbps (automatic detection, no combined system)
Fieldbus: Local bus gateway
Max. number of local bus devices 61 (The on-board I/Os are two devices)

System limits
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 61 (The on-board I/Os are two devices)
Number of devices with parameter channel max. 8
Number of supported branch terminals with remote bus branch 0
Module
ID code (hex) none
Input address area 8 bit
Output address area 4 bit
Register length 16 bit

Digital:
Input name Digital inputs
Description of the input EN 61131-2 type 1
Number of inputs 8
Connection method Inline connector
Connection technology 3-conductor
Input voltage 24 V DC
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input voltage UIN 24 V DC
Nominal input current at UIN typ. 3 mA
Typical input current per channel typ. 3 mA
Typical response time approx. 500 µs
Delay at signal change from 0 to 1 1.2 ms
Delay at signal change from 1 to 0 1.2 ms
Protective circuit Reverse polarity protection; Suppressor diode

Digital:
Output name Digital outputs
Connection method Inline connector
Connection technology 3-conductor
Number of outputs 4
Protective circuit Short-circuit and overload protection; Free running circuit
Output voltage 24 V DC -1 V (At nominal current)
Maximum output current per module max. 2 A

IL EIP BK DI8 DO4 2TX-PAC - Bus coupler

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.