AXL F BK PB - Bus coupler
AXL F BK PB - Bus coupler
2688530
Axioline F, Bus coupler, PROFIBUS DP, D-SUB-9 female connector, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector
The bus coupler is intended for use within a PROFIBUS network and represents the link to the Axioline F I/O system. Up to 63 Axioline F devices can be connected to the bus coupler. A corresponding GSD file is available for integrating the Axioline F station into the programming system. It can be downloaded at: phoenixcontact.net/product/2688530
Dimensional drawing
Width 45 mm
Height 126.1 mm
Depth 74 mm
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
PROFIBUS DP
Number of interfaces 1
Connection method D-SUB-9 female connector
Transmission speed 9.6 kbps ... 12 Mbps
Axioline F local bus
Number of interfaces 1
Connection method Bus base module
Transmission speed 100 Mbps
Service
Number of interfaces 1
Connection method Micro USB type B
Fieldbus: Local bus gateway
Max. number of local bus devices 63 (Consider the logic current consumed by the devices)
System limits
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 63
Product type I/O component
Product family Axioline F
Type block modular
Mounting position any (observe temperature derating)
Scope of delivery including bus base module and Axioline F connector
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)
Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 567 mA (with 2 A at UBus for the I/Os and UL = 24 V)
Power consumption max. 13.7 W (2.0 A on UBus, UL = 24 V)
Protective circuit Surge protection; electronic
Reverse polarity protection; electronic
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Power supply unit 2 A
Electrical isolation/isolation of the voltage ranges
Test voltage: PROFIBUS interface / 24 V communications voltage (UL) feed-in 500 V AC, 50 Hz, 1 min.
Test voltage: PROFIBUS interface / functional ground 500 V AC, 50 Hz, 1 min.
Test voltage: 24 V communications voltage (UL) feed-in / functional ground 500 V AC, 50 Hz, 1 min.
Connection technology
Connection name Axioline F connector
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor connection
Connection method Push-in connection
Conductor cross section rigid 0.2 mm² ... 1.5 mm²
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Axioline F connector
Connection method Push-in connection
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Conductor cross section AWG 24 ... 16
Stripping length 8 mm
Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.
- Overview of electric vehicle charging station construction specifications and requirementsDescription : Regarding the safety protection issues that need to be paid attention to in car charging piles : 1 ." "
- PT 1,5 S-3L - Multi-level terminal blockPT 1,5/S-3L - Multi-level terminal block 3213713 Multi-level terminal block , nom ." "
- TTC-6-2XTVSD-24DC-PT - Surge protection deviceTTC-6-2XTVSD-24DC-PT - Surge protection device 2906808 Fine surge protection for two signal wires with common reference potential ." "
- Q-FSMA-KT - F-SMA connectorQ-FSMA-KT - F-SMA connector 1885994 QUICKON-FSMA plug , for polymer fibers , 4-part set Product type Fiber optic connector ( cable side ) Type FSMA Number" "