D-LAN-CAT.5E Surge protection device

2858991

Fine surge protection in accordance with Class D (CAT.5e), for token ring and Ethernet. RJ45 attachment plug with separate grounding cable, incl. RJ45 cable

Product type Surge protection for information technology
Product family DATATRAB
IEC test classification C1
C2
C3
B2
B3
VDE requirement class C1
C2
C3
B2
B3
Type Attachment plug
Surge protection fault message none
Insulation characteristics
Overvoltage category II
Pollution degree 2

Connection method RJ45

Dimensional drawing
Width 25.4 mm
Height 94 mm
Depth 25.4 mm

Color black (RAL 9005)
Housing material Aluminum, anodized

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Shield & Shield-Earth Ground
Maximum continuous voltage UC ± 7 V DC
Rated current 1.5 A (25 °C)
Operating effective current IC at UC ≤ 100 µA
Residual current IPE ≤ 100 µA
Nominal discharge current In (8/20) µs (line-line) 350 A
Nominal discharge current In (8/20) µs (line-ground) 2.5 kA
Max. discharge current Imax (8/20) µs maximum (line-earth) 2.5 kA (in total)
Nominal pulse current Ian (10/700) µs (line-line) 160 A
Nominal pulse current Ian (10/700) µs (line-earth) 160 A
Output voltage limitation at 1 kV/µs (line-line) spike ≤ 22 V
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 80 V (equipotential bonding lead: 1 m)
Output voltage limitation at 1 kV/µs (shield-ground) spike ≤ 700 V (equipotential bonding lead: 1 m)
Residual voltage at In (conductor-conductor) ≤ 45 V
Residual voltage at In (conductor-ground) ≤ 45 V
Residual voltage at In (shield-ground) ≤ 700 V
Voltage protection level Up (line-line) ≤ 50 V (C1 - 500 V / 250 A)
≤ 20 V (B3 - 2 kV / 25 A)
Voltage protection level Up (line-earth) ≤ 65 V (C1, 500 V/250 A - PA-Ltg: 1 m)
≤ 25 V (B3 - 2 kV / 25 A - PA-Ltg: 1 m)
≤ 60 V (C3, 7 kV/90 A - PA-Ltg: 1 m)
Voltage protection level Up (shield-ground) ≤ 850 V (C2 - 4 kV/2 kA - PA-Ltg: 1 m)
Response time tA (line-line) ≤ 500 ns
Response time tA (line-earth) ≤ 100 ns
Input attenuation aE, sym. 1 dB (up to 100 MHz, 100 Ω system)
Near-end crosstalk attenuation 36 dB (pair 3-6 against pair 4-5 in 100 Ω system / 100 MHz)
40 dB (all other pair combinations in 100 Ω system/100 MHz)
Cut-off frequency fg (3 dB), sym. in 100 Ω system ≤ 100 MHz
Capacity (Core-Core) 20 pF (typical)
Capacity (Core-Earth) 1 pF (typical)

D-LAN-CAT.5E - Surge protection device

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.

  • PSR-PC20-1NO-1NC-24DC-SP - Coupling relayPSR-PC20-1NO-1NC-24DC-SP - Coupling relay
    PSR-PC20-1NO-1NC-24DC-SP - Coupling relay 2700578 Coupling relay for SIL 3 high - and low-demand applications , couples digital output signals to the" "
  • PSR-MC72-2NO-1DO-24DC-SC - Safety relaysPSR-MC72-2NO-1DO-24DC-SC - Safety relays
    PSR-MC72-2NO-1DO-24DC-SC - Safety relays 2702096 Safety relay for emergency stop , safety doors , light grid up to SIL 3 , Cat ." "
  • PSR-MC72-2NO-1DO-24DC-SP - Safety relaysPSR-MC72-2NO-1DO-24DC-SP - Safety relays
    PSR-MC72-2NO-1DO-24DC-SP - Safety relays 2702097 Safety relay for emergency stop , safety doors , light grid up to SIL 3 , Cat ." "
  • PSI-MOS-PROFIB FO1300 E - FO convertersPSI-MOS-PROFIB FO1300 E - FO converters
    PSI-MOS-PROFIB/FO1300 E - FO converters 2708559 Fiber optic converter with integrated optical diagnostics , alarm contact , for PROFIBUS up to 12 Mbps ," "