SACC-PO12MSX-8CT-CL SH Data connector

1021783

Data connector, Ethernet CAT6A (10 Gbps), PROFINET CAT6A (10 Gbps), 8-position, shielded, Plug straight M12 Push-Pull, coding: X, Crimp connection, knurl material: PA 6.6, external cable diameter 6.5 mm ... 10 mm, without crimp contacts

General This product corresponds to the PROFINET Cabling and Interconnection Technology Guideline for PROFINET regulations, version 2.00, order no: 2.252, Chapter 8.2 Connectors for Outside Environment (Balanced cabling)
Assembly instruction: NOTE: Observe the permissible bending radii when laying conductors, since the degree of protection may be put in jeopardy if the bending forces are too high. Alleviate mechanical loads upstream of the connector, e.g. by using cable ties.

Assembly instructions Contacts can be clipped in place and unclipped without tools

Product type Circular connector (cable-side)
Application Data
Sensor type Ethernet
Number of positions 8
No. of cable outlets 1
Shielded yes
Coding X
Cable outlet straight
Insulation characteristics
Overvoltage category II
Degree of pollution 3

Dimensional drawing
Length 44 mm
Wrench size, union nut 15 mm
Wrench size, counter nut 14 mm
External dimensions
Outside diameter 6.5 mm ... 10 mm
Housing
Diameter housing 22 mm

Flammability rating according to UL 94 V0
Seal material NBR
Material of grip body Zinc die-cast, nickel-plated
Contact carrier material PA 6.6
Material for screw connection PA 6.6
Standards/regulations PA 6.6: Fire protection in rail vehicles - requirement sets R22, R23, R24, and R26 acc. to DIN EN 45545-2 (Risk level HL1 - HL3)

Conductor connection
Connection method Crimp connection
Connection cross section 0.14 mm² ... 0.34 mm² (flexible)
Connection cross section AWG 26 ... 22 (flexible)
Stripping length of the individual wire 4 mm +0,5 mm
Tightening torque 4 Nm (Pressure nut with coupling sleeve)

Rated surge voltage 0.8 kV
Insulation resistance ≥ 100 MΩ
Nominal voltage UN 48 V AC
60 V DC
Nominal current IN 0.5 A

Mechanical data
Insertion/withdrawal cycles ≥ 100

Connection 1
Head design Plug
Head cable outlet straight
Head thread type M12
Head locking type Push-Pull
Coding X

Signal type/category Ethernet CAT6A (IEC 11801), 10 Gbps
PROFINET CAT6A (IEC 11801), 10 Gbps
Stripping length of the individual wire 4 mm +0,5 mm

Ambient conditions
Degree of protection IP65
IP67
IP68
IP69K
Ambient temperature (operation) -40 °C ... 85 °C (Plug / socket)

SACC-PO12MSX-8CT-CL SH - Data connector

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.

  • PSR-PC20-1NO-1NC-24DC-SP - Coupling relayPSR-PC20-1NO-1NC-24DC-SP - Coupling relay
    PSR-PC20-1NO-1NC-24DC-SP - Coupling relay 2700578 Coupling relay for SIL 3 high - and low-demand applications , couples digital output signals to the" "
  • PSR-MC72-2NO-1DO-24DC-SC - Safety relaysPSR-MC72-2NO-1DO-24DC-SC - Safety relays
    PSR-MC72-2NO-1DO-24DC-SC - Safety relays 2702096 Safety relay for emergency stop , safety doors , light grid up to SIL 3 , Cat ." "
  • PSR-MC72-2NO-1DO-24DC-SP - Safety relaysPSR-MC72-2NO-1DO-24DC-SP - Safety relays
    PSR-MC72-2NO-1DO-24DC-SP - Safety relays 2702097 Safety relay for emergency stop , safety doors , light grid up to SIL 3 , Cat ." "
  • PSI-MOS-PROFIB FO1300 E - FO convertersPSI-MOS-PROFIB FO1300 E - FO converters
    PSI-MOS-PROFIB/FO1300 E - FO converters 2708559 Fiber optic converter with integrated optical diagnostics , alarm contact , for PROFIBUS up to 12 Mbps ," "