MINI MCR-2-T-REL-PT Limit value switch

2905633

Universally configurable temperature limit value switch with N/O relay output for the connection of 2, 3, and 4-conductor resistance thermometers and thermocouples. Configurable via DIP switch or software. Push-in connection technology

Universally configurable temperature limit value switch with relay output and plug-in connection technology for switching temperature limit values. 2, 3, 4-conductor RTD and TC sensors can be processed on the input side. A relay with N/O contact is available on the output side. It is then possible to switch loads up to 250 V AC/DC and max. 6 A. You can configure the device using one of the free software solutions available or your smartphone. Default settings can also be made directly on the device by simply using the DIP switches (see configuration table). The temperature limit value switch supports fault monitoring and NFC communication.

Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Limit value switch
Product family MINI Analog Pro
No. of channels 1
Type Signal conditioner
Configuration DIP switches
Software
App
Insulation characteristics: GB Standard
Overvoltage category II
Pollution degree 2

Functionality
Configuration DIP switches
Software
App

Switching point accuracy < 0.1 %
Step response (0–99%) 300 ms
570 ms
380 ms
300 ms
570 ms
Maximum temperature coefficient 0.01 %/K
Electrical isolation Input/output/power supply
Rated insulation voltage 300 Vrms
Test voltage 3 kV AC (50 Hz, 60 s)
Insulation Reinforced insulation according to IEC/EN 61010-1
Supply
Nominal supply voltage 24 V DC
Supply voltage range 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption 44 mA (12 V DC)
22 mA (24 V DC)
Power consumption 570 mW

Signal
Number of inputs 1
Measurement
Number of inputs 1
Configurable/programmable Yes
Sensor types (RTD) that can be used Pt, Ni, Cu sensors
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L
Available input sources Resistance thermometers
Thermocouples
Temperature measuring range -250 °C ... 2500 °C (RTD)
Temperature measuring range ≥ 20 K (RTD)
Sensor type: 500 °C ... 1820 °C
-230 °C ... 1000 °C
-210 °C ... 1200 °C
-250 °C ... 1372 °C
-200 °C ... 1300 °C
-50 °C ... 1768 °C
-50 °C ... 1768 °C
-200 °C ... 400 °C
-200 °C ... 900 °C
-200 °C ... 600 °C
0 °C ... 2500 °C
0 °C ... 1800 °C
0 °C ... 1800 °C
-200 °C ... 100 °C
-200 °C ... 800 °C
Sensor input current  200 µA (RTD)
Max. permissible overall conductor resistance ≤ 25 Ω (Per line, RTD in 3- or 4-conductor technology)
≤ 50 Ω (adjustable, RTD in 2-conductor technology)
Linear resistance measuring range 0 Ω ... 4000 Ω (RTD)
Linear mV signal range -500 mV ... 500 mV (RTD)
Connection technology 2-, 3-, 4-conductor

Switching: Relay
Number of outputs 1
Contact switching type 1 N/O contact
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC
30 V DC
240 V AC (UL)
Limiting continuous current 6 A AC
4 A DC
Min. switching current 100 mA (12 V DC)
Max. switching current 6 A AC (250 V AC)
4 A DC (30 V DC)
Mechanical service life 2x 107 cycles
Setting range of the response delay 0 s ... 10 s (can be set freely via software)
Internal hysteresis can be set freely via software

MINI MCR-2-T-REL-PT - Limit value switch

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.

  • TTC-6-3-HF-F-M-12DC-UT-I - Surge protection deviceTTC-6-3-HF-F-M-12DC-UT-I - Surge protection device
    TTC-6-3-HF-F-M-12DC-UT-I - Surge protection device 2906769 Surge protection with integrated status indicator and knife disconnection for three signal wires" "
  • IB IL AI 2 SF-230-PAC - Analog moduleIB IL AI 2 SF-230-PAC - Analog module
    IB IL AI 2/SF-230-PAC - Analog module 2861577 Inline , Analog input terminal , Analog inputs : 2 , 0 V ... 10 V , -10 V ... 10 V , 0 mA ... 20 mA , 4 mA" "
  • P-FU 5X20 LED 24-5 - Fuse plugP-FU 5X20 LED 24-5 - Fuse plug
    P-FU 5X20 LED 24-5 - Fuse plug 3209248 Fuse plug , Suitable for terminal blocks with a width of 5.2 mm and above with TG zone , nom ." "
  • SACC-M12MR-5PL M - ConnectorSACC-M12MR-5PL M - Connector
    SACC-M12MR-5PL M - Connector 1424651 Connector , Universal , 5-position , unshielded , Plug angled M12 , coding : A , Push-lock spring connection , knurl" "