Primary-switched STEP POWER power supply for DIN rail and direct mounting, input: 1-phase, output: 5 V DC/2 A

STEP POWER power supplies for distribution boards
The STEP POWER power supply range was developed especially for building automation. The low idling losses and high degree of efficiency ensure maximum energy efficiency. They allow flexible use and can be snapped onto the DIN rail or screwed onto an even surface.

AC operation
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
95 V DC ... 250 V DC
Input voltage range AC 85 V AC ... 264 V AC
Input voltage range DC 95 V DC ... 250 V DC
Voltage type of supply voltage AC/DC
Inrush current < 15 A
Inrush current integral (I2t) < 0.1 A2s
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Mains buffering time typ. 25 ms (120 V AC)
typ. 110 ms (230 V AC)
Current consumption 0.2 A (120 V AC)
0.13 A (230 V AC)
Nominal power consumption 28.9 VA
Power factor (cos phi) 0.44
Typical response time < 0.5 s
Input fuse 1.25 A (slow-blow, internal)
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A ... 16 A (AC: Characteristics B, C, D, K)

Efficiency > 81 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 5 V DC
Output current Imax 3.7 A
Nominal output current (IN) 2 A (-25 °C ... 40 °C permanent)
2.2 A (-25 °C ... 55 °C)
Derating 55 °C ... 70 °C (2.5 %/K)
Protection against overvoltage at the output (OVP) < 10 V DC
Residual ripple < 50 mVPP
Output power 10 W
Maximum no-load power dissipation < 0.4 W
Power loss nominal load max. < 2.6 W
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes

Input
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

Types of signaling LED
Operating voltage display Green LED
Signal output: LED status indicator
Status display "DC OK" LED green
Note on status display UOUT > 4 V: LED is lit
Color green
Note on status display LED on

Number of phases 1.00
Insulation voltage input/output 4 kV AC (type test)
3.75 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input/output 3.75 kV AC (routine test)
4 kV AC (type test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)