Email verifiedBusiness License verified

PLC-RPT- 12DC 21 - Relay Module

2024-05-09T07:21:13Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:216731226955120264991@q1211q.9c12o11m

 

PLC-RPT- 12DC/21 Relay Module

2900316

PLC-INTERFACE, consisting of PLC-BPT.../21 basic terminal block with Push-in connection and plug-in miniature relay with power contact, for mounting on DIN rail NS 35/7,5, 1 changeover contact, input voltage 12 V DC

Notes on operation Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....

Product type Relay Module
Product family PLC-INTERFACE
Application Universal
Operating mode 100% operating factor
Mechanical service life 2x 107 cycles

Maximum power dissipation for nominal condition 0.18 W
Test voltage (Winding/contact) 4 kV AC (50 Hz, 1 min., winding/contact)
Insulation characteristics: Coil/contact
Rated insulation voltage 250 V
Rated impulse withstand voltage 6 kV
Overvoltage category III
Degree of pollution 3

Coil side
Nominal input voltage UN 12 V DC
Input voltage range 9.7 V DC ... 16.8 V DC (20 °C)
Drive and function monostable
Drive (polarity) polarized
Typical input current at UN 15.3 mA
Typical response time 5 ms
Typical release time 8 ms
Protective circuit Reverse polarity protection; Polarity protection diode
Surge protection; Freewheeling diode
Operating voltage display Yellow LED

Switching
Contact switching type 1 changeover contact
Type of switch contact Single contact
Contact material AgSnO
Maximum switching voltage 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage 5 V (100 mA)
Limiting continuous current 6 A
Maximum inrush current 10 A (4 s)
Min. switching current 10 mA (12 V)
Short-circuit current 200 A (conditional short-circuit current)
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
1500 VA (for 250 V AC)
Output fuse 4 A gL/gG NEOZED
Switching capacity 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.1 A (at 220 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)

Connection method Push-in connection
Stripping length 10 mm
Conductor cross section rigid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG 26 ... 14

PLC-RPT- 12DC 21 - Relay Module

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.

  • TTC-6-3-HF-F-M-12DC-UT-I - Surge protection deviceTTC-6-3-HF-F-M-12DC-UT-I - Surge protection device
    TTC-6-3-HF-F-M-12DC-UT-I - Surge protection device 2906769 Surge protection with integrated status indicator and knife disconnection for three signal wires" "
  • IB IL AI 2 SF-230-PAC - Analog moduleIB IL AI 2 SF-230-PAC - Analog module
    IB IL AI 2/SF-230-PAC - Analog module 2861577 Inline , Analog input terminal , Analog inputs : 2 , 0 V ... 10 V , -10 V ... 10 V , 0 mA ... 20 mA , 4 mA" "
  • P-FU 5X20 LED 24-5 - Fuse plugP-FU 5X20 LED 24-5 - Fuse plug
    P-FU 5X20 LED 24-5 - Fuse plug 3209248 Fuse plug , Suitable for terminal blocks with a width of 5.2 mm and above with TG zone , nom ." "
  • SACC-M12MR-5PL M - ConnectorSACC-M12MR-5PL M - Connector
    SACC-M12MR-5PL M - Connector 1424651 Connector , Universal , 5-position , unshielded , Plug angled M12 , coding : A , Push-lock spring connection , knurl" "