Email verifiedBusiness License verified

MACX MCR-PTB - Power and error message module

2024-05-15T06:48:37Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:8111534654849497118510531@q8q10.7c14om

 

MACX MCR-PTB Power and error message module

2865625

Power and fault signaling module with screw connection, including corresponding ME 17,5 TBUS 1,5/ 5-ST-3,81 GY DIN rail connector

Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area

Product type Power module
Product family MACX Analog
Insulation characteristics: GB Standard
Overvoltage category II
Pollution degree 2

Electrical isolation Supply/switching output
Electrical isolation 50 V AC/DC

Signal
Voltage input signal 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
Fuse 5 A (replaceable), slow-blow 250 V AC
Polarization and surge protection Yes

Switching: Relay
Contact switching type 1 changeover contact
Contact material Gold (Au)
Maximum switching voltage 50 V AC (2 A)
30 V DC (2 A)
50 V DC (0.22 A)
Signal
Max. current output signal 3.75 A
Output voltage Input voltage - max 0.8 V at 3.75 A

Connection method Screw connection
Stripping length 7 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm

Ex installation (EPL) Gc
Div. 2

Status display 1 x red LED (error)
2 x green LEDs (PWR1 and PWR2)

Dimensional drawing
Width 17.5 mm
Height 103.6 mm
Depth 113.7 mm
Depth NS 35/7,5 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Color gray (RAL 7042)
Flammability rating according to UL 94 V0 (Housing)
Housing material Polyamide (PA 6.6)

Ambient conditions
Degree of protection IP20 (not assessed by UL)
Ambient temperature (operation) -40 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
ATEX
Identification  II 3 G Ex ec nC IIC T4 Gc X
Certificate PxCIF08ATEX2865625X
UKCA Ex (UKEX)
Identification  II 3 G Ex nA nC IIC T4 Gc X
Certificate PxCIF21UKEX2865625X
IECEx
Identification Ex ec nC IIC T4 Gc
Certificate IECEx IBE 08.0004X
CCC / China-Ex
Identification Ex ec nC IIC T4 Gc
Certificate 2021122303114198
UL, USA/Canada
Identification UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC
Shipbuilding approval
Certificate DNV GL TAA00000AG
EAC Ex
Identification  2Ex ec nC IIC T4 Gc
Certificate BY/112 02.01 TP012 103.01 00078

MACX MCR-PTB - Power and error message module

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.