RIF-2-RPT-LDP-24DC 4X21 EX - Relay Module
RIF-2-RPT-LDP-24DC/4X21/EX - Relay Module
2909741
Pre-assembled relay module consisting of: relay base, function plug-in module, power contact relay, and retaining bracket, approval in accordance with ATEX/IECEx (Zone 2) and Ex Zone Class I, Div. 2, Push-in connection, 4 changeover contacts, Freewheeling diode, Input voltage: 24 V DC
Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area
Product type Relay Module
Product family RIFLINE complete
Application Class I, Division 2
potentially explosive areas
Operating mode 100% operating factor
Mechanical service life approx. 2x 107 cycles
Insulation characteristics
Insulation Basic insulation
Insulation characteristics
Insulation Basic insulation
Overvoltage category III
II (Zone 2)
Maximum power dissipation for nominal condition 1.01 W
Test voltage (Winding/contact) 2.5 kVrms (50 Hz, 1 min., winding/contact)
Test voltage (Contact/contact) 2 kVrms (50 Hz, 1 min., contact/contact)
Rated insulation voltage 250 V AC
Rated surge voltage 2.5 kV
Coil side
Nominal input voltage UN 24 V DC
Input voltage range 19.2 V DC ... 30 V DC (20 °C)
Input voltage range in reference to UN see diagram
Drive and function monostable
Drive (polarity) polarized
Typical input current at UN 42 mA
Typical response time 13 ms
Typical release time 14 ms
Coil voltage 24 V DC
Protective circuit Freewheeling diode
Operating voltage display Yellow LED
Switching
Contact switching type 4 changeover contacts
Type of switch contact Single contact
Contact material AgNi
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (24 mA)
Limiting continuous current 6 A (see diagram)
Maximum inrush current 16 A (20 ms, N/O contacts)
Min. switching current 5 mA (24 V)
Interrupting rating (ohmic load) max. 144 W (at 24 V DC)
124 W (at 48 V DC)
108 W (at 60 V DC)
52 W (at 110 V DC)
48 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity 2 A (at 24 V, DC13)
0.22 A (at 120 V, DC13)
0.11 A (at 250 V, DC13)
1.5 A (at 24 V, AC15)
1.5 A (at 120 V, AC15)
1 A (at 240 V, AC15)
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section rigid 0.14 mm² ... 1.5 mm²
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (Ferrule with plastic sleeve)
0.14 mm² ... 1 mm² (Ferrule with plastic sleeve, two conductors on double terminal block)
Conductor cross section AWG 26 ... 16 (solid)
26 ... 16 (flexible)
Drill hole
Diameter 3.2 mm
Width 31 mm
Height 96 mm
Depth 75 mm
Color gray (RAL 7042)
Flammability rating according to UL 94 V2 (Housing)
Ambient conditions
Degree of protection (Relay base) IP20 (Relay base)
Degree of protection (Relay) RT III (Relay)
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
ATEX
Identification II 3G Ex ec nC IIC T4 Gc
Certificate IBExU17ATEXB014X
Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.
- Crane weighing scale for heavy loads equipmentMultiple Units : These scales can display weight measurements in various units , such as kilograms , pounds , ounces , or newtons , depending on the scale" "
- 833140N Digital Hang LED Scale Hanging Crane ScaleDigital Display : Most crane scales are equipped with a digital display that provides real-time weight readings ." "
- Rhorawill Crane Scale 300kgs Double Accuracy ElectronicCrane weighing scales , also known as crane scales or crane load cells , are specialized weighing devices designed for the purpose of lifting and weighing" "
- OCS-T-300kg Digital Hanging ScaleLCD digital crane mini hanging scale for commercial use The mini hanging scale features a die-cast aluminum casing for added strength ." "