Email verifiedBusiness License verified

IB IL 24 DO 4-2MBD-PAC - Digital module

2024-05-16T05:49:35Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:1112354884834429870555@133qq512.c1211om

 

IB IL 24 DO 4-2MBD-PAC Digital module

2861988

Inline, Digital output terminal, Digital outputs: 4, 24 V DC, connection technology: 3-conductor, transmission speed in the local bus: 2 Mbps, degree of protection: IP20, including Inline connector and labeling field

The terminal is designed for use within an Inline station. It is used to output digital signals.

Width 12.2 mm
Height 140.5 mm
Depth 71.5 mm
Note on dimensions Housing dimensions

Inline local bus
Number of interfaces 2
Connection method Inline data jumper
Transmission speed 2 Mbps

Module
ID code (dec.) 189
ID code (hex) BD
Length code (hex) 41
Length code (dec) 65
Process data channel 4 bit
Input address area 0 Byte
Output address area 4 bit
Register length 4 bit
Required parameter data 3 Byte
Required configuration data 4 Byte

Digital:
Output name Digital outputs
Connection method Spring-cage connection
Connection technology 3-conductor
Number of outputs 4
Protective circuit Overload protection, short-circuit protection of outputs; electronic
Output voltage 24 V DC (US - 1 V)
Limitation of the voltage induced on circuit interruption -46 V ... -15 V
Maximum inrush current max. 1.5 A (for 20 ms)
Maximum output current per channel 500 mA
Maximum output current per module 2 A
Nominal output voltage 24 V DC (voltage difference at Inom ≤ 1 V)
Output voltage when switched off max. 2 V
Output current when switched off max. 300 µA
Nominal load, lamp 12 W
Nominal load, ohmic 12 W (48 Ω)
Maximum operating frequency with ohmic nominal load max. 300 Hz (this switching frequency is limited by the data rate selected, the number of bus devices, the structure of the bus, the software used and the control or computer system used)
Reverse voltage resistance to short pulses Reverse voltage proof
Behavior with overload Auto restart
Behavior with inductive overload Output can be destroyed
Behavior at voltage switch-off The output follows the power supply without delay
Overcurrent shut-down min. 0.7 A
Output current with ground connection interrupt when switched off max. 25 mA

Product type I/O component
Product family Inline
Type modular
Scope of delivery including Inline connector and labeling field
No. of channels 4
Operating mode Process data operation with 4 bits
Diagnostics messages Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)

Potentials: Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current draw max. 65 mA
Power consumption max. 0.49 W
Potentials: Segment circuit supply (US)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 2 A
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC, 50 Hz, 1 min.

IB IL 24 DO 4-2MBD-PAC - Digital module

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.