MCR-SL-S-200-I-LP - Current transducers

2024-05-16T05:56:06Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:1311510412648104298853556@2q7q10.1314co4m

 

MCR-SL-S-200-I-LP Current transducers

2813499

MCR current measuring transducer, for measuring sinusoidal and non-sinusoidal alternating currents, input current 0...200 A, loop-powered output with 4...20 mA


Product type Current transducer
Insulation characteristics
Overvoltage category III
Pollution degree 2

Maximum power dissipation for nominal condition 1 W
Test voltage input/output 4.13 kV AC (50 Hz, 60 s)
Step response (10-90%) < 340 ms
Maximum temperature coefficient < 0.025 %/K
Maximum transmission error < 1 % (of final value)
Rated insulation voltage 300 V AC (to earth)
Supply
Supply voltage range loop-powered, no external supply necessary

Signal
Configurable/programmable Yes
Current input signal 0 A ... 200 A
Measurement
Input current range 0 A AC ... 100 A AC
0 A AC ... 150 A AC
0 A AC ... 200 A AC
Setting range for min. input current 0 A AC ... 100 A AC
Setting range for max. input current 0 A AC ... 200 A AC
Overload capacity Depending on laid conductor
Surge strength Depending on through connected conductor
Frequency measuring range 30 Hz ... 6000 Hz
Curve type Sinusoidal and non-sinusoidal
Operate threshold 1 % (of final value)

Signal: Current
Current output signal 4 mA ... 20 mA
Max. current output signal < 25 mA
Load/output load current output (UB - 12 V) x 350 / 12 A

Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm (4,4 ... 5,31 lbf-in.)
Connection method Through connection

Item dimensions
Width 55 mm
Height 85 mm
Depth 70.5 mm
Circular conductor
Diameter ≤ 18.5 mm

Color green (RAL 6021)
Housing material Polyamide PA non-reinforced

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C

CE
Certificate CE-compliant
UKCA
Certificate UKCA-compliant
UL, USA/Canada
Identification UL/C-UL Listed UL 508
Class I, Div. 2, Groups A, B, C, D T4A
Class I, Zone 2, Group IIC T4A
Or Non-Hazardous Locations only

Mounting type DIN rail mounting
Mounting position any

MCR-SL-S-200-I-LP - Current transducers