Email verifiedBusiness License verified

PT 5-HF-24DC-ST - Surge protection device

2024-05-17T02:34:11Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:01157044108164958214553@2q2q013.c1o13m

 

PT 5-HF-24DC-ST Surge protection device

2906002

PT protective plug with HF protective circuit for 4 signal wires. Nominal voltage: 24 V DC

Product type Surge protection for information technology
Product family PLUGTRAB PT
IEC test classification C1
C2
C3
D1
Type Male
Number of positions 5
Wire pairs per module 2
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal voltage UN 24 V DC

Connection method Screw connection (in connection with the base element)
Screw thread M3
Tightening torque 0.8 Nm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section rigid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12

Dimensional drawing
Width 17.7 mm
Height 45 mm
Depth 52 mm
Horizontal pitch 1 Div.

Color black (RAL 9005)
Flammability rating according to UL 94 V-0
Housing material PA 6.6

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC 28 V DC
Rated current 450 mA (45 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 5 µA (with PT 2X2-BE)
≤ 1 µA (with PT 2X2+F-BE)
Nominal discharge current In (8/20) µs (line-line) 10 kA
Nominal discharge current In (8/20) µs (line-ground) 10 kA (with PT 2X2+F-BE)
10 kA (with PT 2X2-BE)
Pulse discharge current Iimp (10/350) µs 2.5 kA (with PT 2X2-BE)
2.5 kA (with PT 2X2+F-BE)
Total discharge current Itotal (8/20) µs 20 kA
Nominal pulse current Ian (10/1000) µs (line-line) 25 A
Voltage protection level Up (line-line) ≤ 150 V (C1 - 1 kV / 500 A)
≤ 165 V (C2 - 10 kV / 5 kA)
≤ 450 V (C2 - 10 kA)
≤ 50 V (C3 - 25 A)
Voltage protection level Up (line-earth) ≤ 150 V (C1 - 1 kV / 500 A)
≤ 700 V (C1 - 1 kV / 500 A with PT 2X2+F-BE)
≤ 165 V (C2 - 10 kV / 5 kA)
≤ 900 V (C2 - 10 kV / 5 kA with PT 2X2+F-BE)
≤ 450 V (C2 - 10 kA)
≤ 1000 V (C2 - 10 kA with PT 2X2+F-BE)
≤ 50 V (C3 - 25 A)
≤ 800 V (C3 - 25 A with PT 2X2+F-BE)
Voltage protection level Up (line-signalground) ≤ 150 V (C1 - 1 kV / 500 A)
≤ 150 V (C1 - 1 kV / 500 A with PT 2X2+F-BE)
≤ 165 V (C2 - 10 kV / 5 kA)
≤ 165 V (C2 - 10 kV / 5 kA with PT 2X2-BE)
≤ 450 V (C2 - 10 kA)
≤ 450 V (C2 - 10 kV / 5 kA with PT 2X2-BE)
≤ 50 V (C3 - 25 A)
≤ 50 V (C3 - 25 A with PT 2X2-BE)
Response time tA (line-line) ≤ 500 ns
Response time tA (line-earth) ≤ 500 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 13 MHz/100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ω system typ. 70 MHz
Capacity (Core-Core) typ. 23 pF
Resistance per path 2.2 Ω ±10 %
Surge protection fault message none
Max. required back-up fuse 500 mA (T)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m (amsl)

Standards/specifications EN 61643-21/A2
Note 2013
Standards/specifications IEC 61643-21/A2
Note 2012

PT 5-HF-24DC-ST - Surge protection device

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.