Email verifiedBusiness License verified

TTC-6P-2X1-M-24DC-PT-I - Surge protection device

2024-05-17T04:00:49Z 
Company: 上海当临自动化科技有限公司
Location: China - Shanghai,上海市青浦区练西公路2850号1幢
Price: Negotiation
Contact: Jason(Manager)
Contact Me:

Tell:+86-19921425125 Mobile:+86-19921425125 Email:31105949413810404986255012@q05q.7c6o12m

 

TTC-6P-2X1-M-24DC-PT-I Surge protection device

2906753

Surge protection, consisting of protective plug and base element, with integrated status indicator and disconnect knife for two signal wires with common reference potential, e.g., Digital IN/OUT.

Product type Surge protection for MCR technology
Product family TERMITRAB complete
IEC test classification C1
C2
C3
D1
Type DIN rail module, two-section, divisible
Insulation characteristics
Overvoltage category III
Pollution degree 2

Nominal voltage UN 24 V DC

Connection method Push-in connection
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section rigid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12

Dimensional drawing
Width 6.2 mm +0.1 mm
Height 105.8 mm
Depth 100 mm (incl. DIN rail 7.5 mm)

Color (Base element) gray (RAL 7042)
Color (Male connector) light grey (RAL 7035)
Flammability rating according to UL 94 V-0
Insulating material PBT
Housing material PBT

Mechanical data
Open side panel No

Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC 30 V DC
21 V AC
Rated current 600 mA (56 °C)
Operating effective current IC at UC ≤ 5 µA
Residual current IPE ≤ 10 µA
Nominal discharge current In (8/20) µs (line-ground) 5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-earth) ≤ 140 V (C1 - 1 kV / 500 A)
≤ 190 V (C2 - 10 kV / 5 kA)
≤ 45 V (C3 - 25 A)
≤ 50 V (C3 - 100 A)
Voltage protection level Up static (line-earth) ≤ 55 V (C1 - 1 kV / 500 A)
≤ 120 V (C2 - 10 kV / 5 kA)
Response time tA (line-earth) ≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 270 kHz/150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system typ. 960 kHz
Capacity (Core-Earth) typ. 2.2 nF
Resistance per path 1.65 Ω ±20 %
Surge protection fault message optical
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-earth) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-earth) ≤ 300 ms
Additional technical data
Max. total discharge current I total max (8/20) µs 20 kA (1x)

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl)
Permissible humidity (operation) 5 % ... 95 %

Standards/specifications IEC 61643-21
Note 2000 + corrigendum 2001 + A1:2008, modified + A2:2012

TTC-6P-2X1-M-24DC-PT-I - Surge protection device

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.