ELR H5-IES-PT-24DC 500AC-06-T - Hybrid motor starter
ELR H5-IES-PT-24DC/500AC-06-T - Hybrid motor starter
2906058
Hybrid motor starter; functions: Start motor, Reverse motor, Motor protection, Emergency stop, Higher resistance to transient voltages; input: 24 V DC; output: 3~, 500 V AC, 600 mA; connection method: Push-in connection
Product type Hybrid motor starters
Product family CONTACTRON
Operating mode 100% operating factor
Number of phases 3
Motor starter type Reversing starter
Maximum power dissipation for nominal condition 0.4 W
Switching frequency ≤ 2 Hz (Load-dependent)
Maximum power dissipation 1.5 W
Minimum power dissipation 1.1 W
Coordination type 1
Supply
Rated control circuit supply voltage US 24 V DC
Control supply voltage range 19.2 V DC ... 30 V DC
Rated control supply current IS 40 mA
Protective circuit Surge protection
Reverse polarity protection
Insulation characteristics
Rated insulation voltage 500 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (IEC 60947-1/EN 50178) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Control
Input name Control input right/left
Rated actuating voltage UC 24 V DC
Triggering voltage range 19.2 V DC ... 30 V DC
Rated actuating current IC 5 mA
Switching threshold 9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level < 5 V DC (For EMERGENCY STOP)
Typical turn-off time < 30 ms
Protective circuit Reverse polarity protection
AC output
Rated operating voltage Ue 500 V AC
Operating voltage range 42 V AC ... 550 V AC
Rated operating current Ie 0.6 A (AC-51)
0.6 A (AC-53a)
Mains frequency 50/60 Hz
Load current range 75 mA ... 600 mA (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2 Class 10A
Cooling time 20 min.
Leakage current 0 mA
Protective circuit Surge protection
Acknowledge output
Note Confirmation: floating change-over contact, signal contact
Contact switching type 1 changeover contact
Switching capacity in accordance with IEC 60947-5-1 3 A (230 V, AC15)
2 A (24 V, DC13)
Control circuits
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Load circuit
Connection method Push-in connection
Stripping length 10 mm
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Status display Yellow LED
Operating voltage display Green LED
Error indication Red LED
Width 22.5 mm
Height 107.5 mm
Depth 114 mm
Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.
- CY7C68013A-56LTXC.CYPRESSIntroducing the CY7C68013A-56LTXC , the latest in cutting-edge USB technology ." "
- MAX4544EUT+T.MAXhe MAX4544EUT+ is the ultimate solution for all your audio and video signal processing needs ." "
- VNQ7040AYTR.STIntroducing the VNQ7040AYTR , the latest innovation in technology that is sure to take your experience to the next level ." "
- TMS320F28335PGFA.FZXIntroducing the TMS320F28335PGFA , the latest and most advanced microcontroller from Texas Instruments ." "